M.V OIL IMMERSED TRANSFORMERS
IPEL Transformers are manufactured in accordance with the following industry and international standards DIN 42500, VDE 0532 and IEC 76.
Product scope:
- Three Phase
- 50 kVA through 5000 kVA
- Primary Voltages through 36 kV
- Secondary Voltage through 15,75 kV
Typical production:
- Primary Voltage 20 kV
- Secondary Voltage 400V / 231V
- Frequency 50Hz
- Environment Temperature -5oC up to 40 oC
- Insulation class A
IPEL S.A is delivering the Oil immersed Transformers with the following standards:
- HV connections
- LV connections
- Off load tap changer links
- Bucholtz relay
- Dehydrator
- Conservator
- Oil level indicator
- Two contactors thermometer
- Two points for earth connection
- Lifting lugs for safe lifting
- Test Report according to IEC 76 - 726
- Dimension drawing
- Tap changer drawing
- Operating and installation manual
- 12 months guaranty
EXTRAS
- Primary Voltage 15 - 20 kV
- Protection box IP 55
- Arrangement of oil level indicator with electrical contact
|



|
|